Type PY harmonic mitigating Power TransFilters™ exceed all existing and pending energy efficiency requirements under nonlinear loading.
Type PY transformers’ ultra-low Excitation (no-load) Losses provide high efficiency during periods of light-loading (<15% FL). This benefit is achieved by using higher quality, grain-oriented silicon core steel and full and step-lap miter-cut cores with reduced laminations per group.
Unlike Excitation Losses, which are constant from no-load to full-load, Impedance (load) Losses become significant at approximately 15% FL. Excitation and Impedance Losses are approximately equal at 50% FL under linear loading. Type PY transformers exceed the efficiency requirements of DOE 2016 under linear loading. Optional e-RatedÒ units exceed these efficiency requirements under moderate nonlinear loading (≤K-9). Type PY transformers’ published efficiencies can be matched to anticipated or measured average loading above 50% FL, when required.
Type PV Power TransFilter™ Medium Voltage, UL Listed Dry-Type & Cast Coil Transformers for High K-Factor, Phase-to-Neutral Connected Nonlinear Loads with an integrated Type TPM Transformer Performance Meter™
Type PV transformers’ ultra-low Excitation (no-load) Losses provide high efficiency during periods of light-loading (<15% FL). This benefit is achieved by using higher quality, grain-oriented silicon core steel and full and step-lap miter-cut cores with reduced laminations per group.
Unlike Excitation Losses, which are constant from no-load to full-load, Impedance (load) Losses become significant at approximately 15% FL.
Excitation and Impedance Losses are approximately equal at 50% FL under linear loading. Type PV Power TransFilters™ exceed the efficiency requirements of DOE 2016 under linear loading. Optional e-Rated® units exceed these efficiency requirements under moderate nonlinear loading (≤K-13). Type PV transformers’ published efficiencies can be matched to anticipated or measured average loading above 50% FL, when required.
Type PV transformers cancel positive- and negative-sequence harmonic currents at their common primary bus or within their multi-output secondary windings. They are available in a number of standard primary-to-secondary phase-shifts so that they may be used to create twelve-, eighteen- or twenty-four-pulse systems. In addition, Type PV transformer’s secondary windings are configured to cause the cancellation of all load-generated third-order zero-sequence flux in the core’s magnetic circuit.
ISSI is in the business of helping its customers solve their problems in the most economical way. It is our mission to exceed our customer’s expectations through a corporate belief and culture that places their success ahead of our own.